What Happens When a Critical Output Module Fails on a Live Line?
Every maintenance engineer knows the feeling: a discrete output card drops out, and production stops while the team hunts for a replacement. The Schneider 140DAO84220 is the answer for Modicon Quantum systems running AC field devices. This 16-point AC Triac output module delivers reliable switching for low-voltage loads, and Oil AutoTech keeps practical spares ready for oil, gas and industrial automation sites.

Product Overview
The 140DAO84220 belongs to the Schneider Electric Modicon Quantum series. It is a discrete output module with 16 points arranged in four isolated groups of four. Each output uses a bidirectional thyristor (Triac) for AC switching, so it handles inductive and resistive AC loads without mechanical contacts. The module occupies a single slot in the Quantum backplane.
Technical Specifications
Output Channels and Grouping
The 16 points split into 4 groups × 4 channels. Group-to-group isolation lets you mix separate field circuits on one card. Each output carries 4 A rms between 20 and 56 V AC, while the module total reaches 16 A rms and each group handles 4 A rms.
Switching Speed and Diagnostics
A zero-crossing Triac design gives a typical response time of 0.5 ms. LED indication covers blown fuse and loss of field power, so technicians can diagnose faults without pulling the card.
Electrical and Physical Data
The module draws 5 V DC from the backplane at 350 mA. Power consumption is 1.85 W plus 1.1 V multiplied by total load current. Dimensions are 250 × 40.34 × 103.85 mm, weight 0.3 kg, and the protection rating is IP20.

Where the 140DAO84220 Fits
Oil and Gas Skids
AC solenoids, pilot valves and small motor starters on skids often run at low AC voltage. The 4 A rms per output and group isolation suit these mixed loads.
Water and Wastewater
Pump control panels use AC contactors and indicator lamps. The 0.5 ms response keeps sequencing tight.
Packaging and Material Handling
High-cycle AC actuators benefit from Triac switching with no contact wear. This is a practical replacement path for aging output cards, and Oil AutoTech can confirm availability quickly.
Installation and Maintenance Notes
Mount the module in a Quantum backplane slot with adequate panel ventilation. Keep field wiring separated by group to preserve isolation. Inspect LED diagnostics periodically and check fuse condition during scheduled shutdowns. Because the 140DAO84220 is discontinued (End of Sale), verify current lifecycle status and availability with Oil AutoTech before ordering.
Integration and Selection
This module works within Modicon Quantum I/O architectures. When integrating into fieldbus networks, wiring may require an external gateway or connection module; confirm cables and gateways with the supplier. Before buying, verify channel count, group isolation needs, load current per point and backplane slot availability.
FAQs
Is the 140DAO84220 still available?
It is discontinued (End of Sale). Contact Oil AutoTech for current stock and replacement options.
What load current can each output handle?
4 A rms per output from 20 to 56 V AC, with 4 A rms per group and 16 A rms per module.
Does it provide diagnostics?
Yes, LED indication covers blown fuse and loss of field power.
How fast does it switch?
Typical response time is 0.5 ms with zero-crossing Triac operation.
How many slots does it need?
One slot in the Modicon Quantum backplane.