Room 7A, No. 59 Hubin North Road, Siming District, Xiamen City, China sales@oilautotech.com +86 181 5089 9927

Allen-Bradley

1756-OW16I | Allen-Bradley ControlLogix 16-Point Isolated Relay Output Module

  • Model 1756-OW16I
  • Type I/O Modules
  • Condition In Stock
4.6/5 (16 reviews)
$257.00 Indicative price · request a quote for availability

Allen-Bradley 1756-OW16I ControlLogix isolated relay output module with 16 normally open contacts. Ready-to-ship spares for oil, gas and industrial automation.

Product Description

Product Overview

Downtime on a ControlLogix line rarely waits for a purchase order. The Allen-Bradley 1756-OW16I is a ControlLogix discrete output module built around Sixteen (16) Normally Open (N.O.), individually isolated relay contacts. Because each channel is isolated, one field fault cannot drag the rest of the card down with it — a practical advantage when you are running mixed AC and DC loads on the same chassis.

This is a dry-contact output module, not a solid-state sourcing card. That distinction matters when you need to switch real-world devices rather than logic-level signals.

Figure 1: Front view of the Allen-Bradley 1756-OW16I industrial automation component showing its physical design and enclosure.

Technical Specifications

Parameter Value
Series ControlLogix
Outputs 16, individually isolated
Contact form Normally Open (N.O.)
Operating voltage 5–125V DC; 10–240V AC
Output current 1 A @ 5–30V DC; 0.5 A @ 48V DC; 0.22 A @ 125V DC; 1.5 A @ 120V AC 50/60 Hz; 0.75 A @ 240V AC 50/60 Hz
Backplane current @ 5.1V 150 mA
Total backplane power 4.4 W
Power dissipation 4.5 W @ 60 °C (140 °F)
Signal delay 10 ms max, both transitions
Isolation voltage 50 V continuous
Terminal block 1756-TBCH; 1756-TBS6H
Enclosure None (open-style)

What the Ratings Mean in Practice

The dual AC/DC operating window lets one card drive 120V AC pilot devices and low-voltage DC solenoids without a separate interface. The 10 ms maximum output delay suits general discrete control; it is not intended for high-speed registration. The 4.5 W dissipation at 60 °C tells you panel thermal planning matters in dense racks.

Where the 1756-OW16I Fits

Oil and gas skids. Isolated contacts separate field wiring from control-side circuits, which simplifies troubleshooting when a valve or heater circuit misbehaves.

Packaging and material handling. Mixed AC/DC loads on one module reduce spare-part count — one card covers several device types.

Upgrade and replacement work. When an older relay output card reaches end of service, the 1756-OW16I slots into ControlLogix chassis positions and keeps existing field wiring largely intact, provided terminations match.

Figure 2: Technical layout and connection details for the Allen-Bradley 1756-OW16I industrial automation component.

Integration Notes

This module is a ControlLogix platform card. Wiring into a networked architecture may require an external gateway or connection module depending on your topology. Confirm cables, terminal blocks and gateways with your supplier before ordering.

Applicable removable terminal blocks are 1756-TBCH and 1756-TBS6H. The module ships with an RTB.

Selection Checklist

Before you buy, confirm:

  • Chassis slot and ControlLogix compatibility
  • Whether your loads are AC, DC, or mixed
  • Contact current against your actual device inrush
  • Terminal block part number you need
  • Panel thermal headroom for 4.5 W per module

Please verify current lifecycle status and availability with Oil AutoTech before ordering. As a supplier focused on oil, gas and industrial automation, Oil AutoTech offers hands-on technical selection help and fast dispatch, worldwide.

Comparison at a Glance

Feature 1756-OW16I (this model) Typical solid-state DC output
Contact type Isolated N.O. relay Solid-state sourcing
AC and DC loads Both DC only
Channel isolation Individually isolated Usually commoned
Switching speed 10 ms max delay Faster
Best for Mixed loads, isolation High-speed DC switching

If your application needs isolated dry contacts across AC and DC, the 1756-OW16I is the practical pick. If you need microsecond switching, a solid-state card is the better fit.

Contact Oil AutoTech today for pricing and availability.

Specifications

Model / No. 1756-OW16I
Product Type I/O Modules
Brand Allen-Bradley
Condition In Stock
Origin US
Warranty 12 Month
Price $257.00

Additional Information

Mfr. Part Number:
1756-OW16I
Manufacturer: Allen-Bradley / Rockwell Automation
Description: Allen-Bradley 1756-OW16I ControlLogix Isolated Relay Output Module 16-Points
Full Description: Allen-Bradley 1756-OW16I ControlLogix Normally Open Isolated Relay Output Module, 16 Points (36 Pin) The Allen-Bradley 1756-OW16I is a ControlLogix Discrete output module that features Sixteen (16) Normally Open (N.O.), individually isolated contact outputs. Each contact output has a operating voltage range of 5-125VDC and 10-240VAC. It delivers output current ratings of 1 A @ 5-30VDC; 0.5 A @ 48VDC; 0.22 A @ 125VDC; 1.5 A @ 120VAC, 50/60 Hz and 0.75 A @ 240VAC, 50/60 Hz. Technical specifications for 1756-OW16I
Manufacturer Rockwell Automation
Module Type Digital DC Sourcing Output
Series ControlLogix
Part Number/Catalog No. 1756-OW16I
Brand Allen-Bradley
No. of outputs Sixteen (16), individually isolated channels
Contact form Normally Open (N.O.)
Operating Voltage range 5…125V DC; 10…240V AC
Output Voltage range 1 A @ 5…30V DC; 0.5 A @ 48V DC; 0.22 A @ 125V DC; 1.5 A @ 120V AC 50/60 Hz; 0.75 A @ 240V AC 50/60 Hz
Current draw @ 5.1V 150 mA
Total backplane Power 4.4 W
Backplane Current, 24VDC 2 mA
Power Dissipation 4.5 W @ 60 °C (140 °F)
Output Signal delay, OFF to ON 10 ms, max
Output Signal delay, ON to OFF 10 ms max
Enclosure type rating None (open-style)
Removable Terminal Block 1756-TBCH; 1756-TBS6H
Outputs 16-Point Individually Isolated
Operating Voltage 10-265 Volts AC, 5-150 Volts DC
Output Current 2, 0.5, 0.25 Amps
Maximum Output Delay Time 10 milliseconds
Contact Output 13 N.O.
Power Dissipation (Max) 4.5 Watts at 60 Celsius
Backplane Current at 5 Volts 150 milliamps
Backplane Current at 24 Volts 150 milliamps
Removeable Terminal Block(s) 1756-TBCH, 1756-TBS6H
Isolation Voltage 50 Volts Continuous
Enclosure None
UPC 10612598171467 Description
The Allen-Bradley 1756-OW16I is a Sixteen (16) channel discrete output module that is part of the ControlLogix automation platform. This module is a relay output module with contact form of Normally Open (N.O.) with individual isolation. This module may also be termed as a dry contact output module which is compatible to be operated at voltage ranges of 5-125VDC and 10-240VAC.

The 1756-OW16I delivers output current ratings of 1 A @ 5-30V DC; 0.5 A @ 48VDC; 0.22 A @ 125VDC; 1.5 A @ 120VAC, 50/60 Hz and 0.75 A @ 240VAC, 50/60 Hz. This module has a pilot duty rating of C300/R150.

Each output channel has a maximum output delay time of 10 ms for both signal transitions. It draws 150 mA current from the backplane @ 5.1 VDC and 24VDC with total backplane power draw of 4.4 Watts.

The 1756-OW16I has a maximum switching frequency of One (1) operation every Three (3) seconds or (0.3 Hz at rated load) with mean bounce time of 1.2 ms. Each of the output contacts are expected to operate up to 300 kHz when used with resistive loads and 100 kHz when used with inductive loads. Additionally, this module supports scheduled outputs and may be configured to Hold last state, On or Off during when FAULTED with Off as default setting. Similarly, output states may also be held at last state, with OFF as default setting during PROGRAM mode. This module is shipped with a Removable Terminal Block (RTB). Applicable RTB for use with this module are 1756-TBCH and 1756-TBS6H.

The 1756-OW16I’s output delay time for both ON to OFF and OFF to ON is 10 milliseconds and it draws a backplane current of 150mA at both 5.1 Volts and 24 Volts DC and it has a total backplane power of 4.4 Watts. It has a thermal dissipation of 15.35 BTU/hour and dissipates 4.5 Watts at 60 degrees Celsius. Each output can accommodate a minimum current load of 10mA and a current leakage of 1.5 mA per point. The 1756-OW16I contact module has an initial contact impedance of 100 Ohms at 6V, 1A and it has a load-dependent switching frequency of 0.3 Hertz. It has a mean bounce time of 1.2 milliseconds with an expected contact life of 300 kHz resistive and of 100 kHz inductive. The 1756-OW16I has a scheduled output with a 16.7 second synchronization time with respect to Coordinated System Time (CST), and it has a circuit isolation voltage of 250 Volts with a basic insulation type tested at 1350 Volts AC for 2 seconds between outputs-to-backplane and output-to-output. The 1756-OW16I has a designated T4 North America temperature code and an open enclosure. Its operational temperature ranges between 0 and 60 degrees Celsius at a humidity of 5 to 95% without condensation.

Shipping & Returns

Shipping Port
Xiamen
Shipping Details
Ships within 1-3 business days after payment via DHL / FedEx / UPS Express, or by sea/air freight for bulk orders. Tracking number is provided the same day the parcel leaves our warehouse.
Return Policy
30-day return for unused items in original packaging. All parts are covered by a 12-month warranty against defects; DOA units are replaced free of charge.

Downloads

Download Instruction Manual (Allen-Bradley_1756_1756-OW16I_Service_Manual)

Latest News